Eaton – 210+ Electronic Trip Units

The Series C F-Frame molded-case circuit breaker is equipped with the 210+ electronic trip unit and features LSI and LI protection settings. The F-Frame breaker is NEMA, UL and CSA listed.

For installation in assemblies such as panelboards, switchboards, motor control centers, switchgear and machinery control panels, the 210+ electronic trip units are available in two types, LI and LSI. Both versions include a seven-position dial to set current rating (ampacity) of the breaker. The LI version also includes an adjustable instantaneous protection setting. The LSI version includes a short delay setting with magnitude and time delay options to improve coordination when protecting against electrical faults in a system.

Available features on the new electronic trip unit include two dials for simplified setup during installation, including an ampacity dial with seven ANSI ratings on each frame; tighter tolerances on protection curves from thermal magnetic breakers; a status indication light to provide user situational awareness; a test port for secondary injection testing; and a tamper-protection clear cover with a slot for a wire seal.

Three frame sizes with multiple ratings each

  • 100A: 40A – 100A (LI and LSI)
  • 150A: 70A – 150A (LI only)
  • 225A: 100A – 225A (LI and LSI)

PM3 Connectivity

  • INCOM Communications
  • MODBUS Communications